-40%

Telemecanique (Schneider) LUCB05FU, TeSys U, Advanced Control Unit, NOS

$ 42.24

Availability: 121 in stock
  • Type: Control Unit
  • All returns accepted: Returns Accepted
  • Custom Bundle: No
  • Restocking Fee: No
  • Current Type: AC/DC
  • Item must be returned within: 30 Days
  • Voltage: 88/264 V
  • Condition: New
  • Packaging: Box
  • MPN: LUCB05FU
  • Brand: Telemecanique
  • Series: TeSys U
  • Refund will be given as: Money Back
  • Current Rating: Varies
  • Return shipping will be paid by: Seller

    Description

    First, And this is important.
    I’ve been selling on eBay for over 20 years and have had no Negative reviews. ALWAYS POSITIVE.
    Any Item may be returned within 30 days of delivery.
    If you have any issue with it, send it back for a refund (I’ll even eat the return shipping).
    There is absolutely NO Risk.
    These are BRAND NEW old stock in original boxes.
    My price is the best on the net (that I can find) "With Free Shipping"
    Look for yourself
    Contact me if you have a big project and need the whole lot of 121 pieces. I'll change the listing and let them all go for 00
    That's 80 off (and still free shipping). I may even have 1 or 2 open box extras I'll throw in.
    Complementary
    control circuit voltage limits
    88...264 V for AC circuit 110...240 V in operation
    88...242 V for DC circuit 110...220 V in operation
    55 V for AC circuit 110...240 V drop-out
    55 V for DC circuit 110...220 V drop-out
    typical current consumption
    280 mA 110...240 V AC I maximum while closing with LUB12
    280 mA 110...240 V AC I maximum while closing with LUB32
    280 mA 110...240 V AC I maximum while closing with LUB38
    280 mA 110...220 V DC I maximum while closing with LUB12
    280 mA 110...220 V DC I maximum while closing with LUB32
    280 mA 110...220 V DC I maximum while closing with LUB38
    35 mA 110...240 V AC I rms sealed with LUB12
    25 mA 110...240 V AC I rms sealed with LUB32
    25 mA 110...240 V AC I rms sealed with LUB38
    35 mA 110...220 V DC I rms sealed with LUB12
    25 mA 110...220 V DC I rms sealed with LUB32
    25 mA 110...220 V DC I rms sealed with LUB38
    heat dissipation
    2 W control circuit with LUB12
    3 W control circuit with LUB32
    3 W control circuit with LUB38
    operating time
    35 ms opening with LUB12 for control circuit
    35 ms opening with LUB32 for control circuit
    35 ms opening with LUB38 for control circuit
    50 ms closing with LUB12 control circuit
    50 ms closing with LUB32 for control circuit
    50 ms closing with LUB38 for control circuit
    reset
    Manual reset
    standards
    EN 60947-6-2
    IEC 60947-6-2
    UL 60947-4-1, with phase barrier
    CSA C22.2 No 60947-4-1, with phase barrier
    product certifications
    range
    TeSys
    range of product
    TeSys U
    product name
    TeSys U
    device short name
    LUCB
    product or component type
    Advanced control unit
    device application
    Motor control
    Motor protection
    product specific application
    Basic protection and advanced functions, communication
    main function available
    Protection against overload and short-circuit
    Earth fault protection
    Protection against phase failure and phase imbalance
    Manual reset
    product compatibility
    Power base LUB12
    Power base LUB32
    Power base LUB38
    Power base LUB120
    Power base LUB320
    Power base LUB380
    Reversing contactor breaker LU2B12FU
    Reversing contactor breaker LU2B32FU
    Reversing contactor breaker LU2B38FU
    [Ue] rated operational voltage
    690 V AC
    network frequency
    40...60 Hz
    load type
    3-phase motor - cooling: self-cooled
    utilisation category
    AC-41
    AC-44
    AC-43
    motor power kW
    1.5 kW 400...440 V AC 50/60 Hz
    2.2 kW 500 V AC 50/60 Hz
    3 kW 690 V AC 50/60 Hz
    rated motor current adjustment range
    1.25…5 A
    thermal overload class
    Class 10 40…60 Hz -13…158 °F (-25…70 °C) IEC 60947-6-2
    Class 10 40…60 Hz -13…158 °F (-25…70 °C) UL 508
    tripping threshold
    14.2 x Ir +/- 20 %
    phase failure sensitivity
    Yes
    [Uc] control circuit voltage
    110...240 V AC
    110...220 V DC